Entelar Energy Inverter, Smart Energy Controller, Three Phase, Max output 20,000w
- Description
- Key Features
- Technical Specifications
The Entelar EESOLAR-20KTL-MB0 is a three-phase Smart Energy Controller designed for commercial and large residential solar + storage installations. With battery terminal support, active safety features (including AI-powered active arcing protection), and high efficiency, it delivers reliable, high-yield performance. Optimised to pair with Entelar’s EESTORE battery modules and smart string optimisers, it offers up to 30% more energy when fully optimised.
-
AI-powered Active Arcing Protection to enhance safety on PV string inputs.
-
Battery-ready: includes 2 battery terminals, compatible with EESTORE-5-30 modules.
-
“Higher Yields” with support for full optimisers, up to ~30% energy gain in certain conditions.
-
Dual MPPTs with flexible input string configuration.
-
Wide voltage range and robust protection: IP66, supports harsh NZ environmental conditions.
| Specification | Value |
|---|---|
| Rated Output Power (AC) | 20,000 W |
| Max Apparent Power | 22,000 VA |
| MPPTs / Number of Inputs | 2 MPPTs, 4 inputs |
| Max DC Input / PV Open-Circuit Voltage | 1,100 V DC |
| MPPT Voltage Operating Range | ~ 200 V to ~ 1,000 V DC (start-up ≈ 200 V) |
| Full-load MPPT Voltage Range | ≈ 410-800 V DC |
| Max Input Current per MPPT | 30 A (two strings) / 20 A (single string) |
| Short-Circuit Current | 40 A |
| Battery Charge / Discharge Capability | Charge up to ~25 kW with two strings; Discharge up to ~22 kW |
| Rated Output Voltage (AC) | 3-phase, 3W / N + PE. Voltages e.g. 220/380 V, 230/400 V, 240/415 V depending on region |
| Rated AC Current | ~ 30.4 A @ 380 Vac; somewhat lower at higher nominal voltages |
| Max Output Current | ~ 33.6 A @ 380 Vac etc. |
| Efficiency (Max / European Weighted) | ~ 98.4% peak; ~ 98.1% weighted European efficiency |
| Temperature Range (Operating) | -25 °C to +60 °C |
| Humidity / Environmental | 0-100% RH non-condensing; IP66 enclosure; altitude up to ~ 4,000 m (with derating above ~2,000 m) |
| Protection Features | Anti-islanding; DC reverse polarity; DC & AC surge protection (Type II); Arc fault detection; residual current monitoring |
| Communication & Display | LED indicators; RS-485; WLAN/Ethernet via EEDongleA-05 |
| Physical Dimensions & Weight | ~ 546 × 460 × 241.5 mm; ~ 21 kg |
| Standards / Compliance | AS/NZS 4777.2:2020, IEC 62109-1&2, etc. |